Standard ABC Cable Specifications
| Model specification | Phase Core | Neutral Core | Complete Cable | |||||||||
| No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | Overall Diameter (Approx.) | Weight (Approx.) | |||
| MIN | MAX | MIN | MAX | |||||||||
| ABC 2X16 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 14.2 | 127 |
| ABC 4X16 | 3X16 | 7 | 4.6 | 5.1 | 1.2 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 17.1 | 253 |
| ABC 2X25 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 17.2 | 193 |
| ABC 4X25 | 3x25 | 7 | 5.8 | 6.3 | 1.4 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 20.8 | 387 |
| ABC 2X35 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 20.2 | 263 |
| ABC 4X35 | 3x35 | 7 | 6.8 | 7.3 | 1.6 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 24.4 | 527 |
| ABC 2X50 | 1x50 | 7 | 7.9 | 8.4 | 1.6 | 1x50 | 7 | 7.9 | 8.4 | 1.6 | 21.8 | 338 |
ABC Cable with AAAC Messenger Core Specifications
| Model specification | Phase Core | Neutral Core | Complete Cable | |||||||||
| No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | Overall Diameter (Approx.) | Weight (Approx.) | |||
| MIN | MAX | MIN | MAX | |||||||||
| ABC 3X25+54.6 | 3x25 | 7 | 5.8 | 6.3 | 1.4 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 23.2 | 491 | |
| ABC 3X35+54.6 | 3x35 | 7 | 6.8 | 7.3 | 1.6 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 26 | 596 | |
| ABC 3X50+54.6 | 3x50 | 7 | 7.9 | 8.4 | 1.6 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 27.7 | 708 | |
| ABC 3X70+54.6 | 3x70 | 19 | 9.7 | 10.2 | 1.8 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 31.9 | 937 | |
| ABC 3X70+70 | 3x70 | 19 | 9.7 | 10.2 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | 32.5 | 943 | |
| ABC 3X95+54.6 | 3x95 | 19 | 11 | 12 | 1.8 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 35 | 1174 | |
| ABC 3X95+70 | 3x95 | 19 | 11 | 12 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | 35.6 | 1214 | |
| ABC 3X120+70 | 3x120 | 19 | 12.5 | 13.5 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | 37.6 | 1424 | |
| ABC 3X150+70 | 3x150 | 19 | 13.9 | 15 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | 40.7 | 1679 | |
ABC Cable with AAAC Messenger & Lighting Cores Specifications
| Model specification | Phase Core | Neutral Core | Complete Cable | |||||||||
| No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | Overall Diameter (Approx.) | Weight (Approx.) | |||
| MIN | MAX | MIN | MAX | |||||||||
| ABC 3X25+54.6+kx16 | 3x25 | 7 | 5.8 | 6.3 | 1.4 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X35+54.6+kx16 | 3x35 | 7 | 6.8 | 7.3 | 1.6 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X50+54.6+kx16 | 3x50 | 7 | 7.9 | 8.4 | 1.6 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X70+54.6+kx25 | 3x70 | 19 | 9.7 | 10.2 | 1.8 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X70+70+kx25 | 3x70 | 19 | 9.7 | 10.2 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | / | / | |
| ABC 3X95+54.6+kx16 | 3x95 | 19 | 11 | 12 | 1.8 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X95+70+kx16 | 3x95 | 19 | 11 | 12 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | / | / | |
| ABC 3X120+70+kx16 | 3x120 | 19 | 12.5 | 13.5 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | / | / | |
| ABC 3X150+70+kx16 | 3x150 | 19 | 13.9 | 15 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | / | / | |
Lighting Cores Note: Users can add one or two lighting wires to the above product structure according to their own needs. The specifications of the lighting wires are 16mm² and 25mm².
Frequently Asked Questions (FAQ)
What configurations are available for standard ABC cables?
Standard Aerial Bundled Cables (ABC) are available in 2-core and 4-core configurations. Phase core sizes range from 1X16mm² up to 3X50mm², depending on the model specification and power requirements.
What types of Neutral Cores are used in these specifications?
Depending on the model, the neutral core can either be a standard copper/aluminum core matching the phase size (e.g., 1x25) or an All Aluminium Alloy Conductor (AAAC) messenger core (e.g., AAAC 54.6 or AAAC 70) which provides additional mechanical support.
Can street lighting wires be integrated into the ABC cables?
Yes, users can customize the cable structure by adding one or two lighting wires based on application needs. The standard specifications for these integrated lighting wires are 16mm² and 25mm².
What is the range of insulation thickness for these cables?
The insulation thickness varies by core size to ensure safety and durability. It typically ranges from 1.2mm for 16mm² conductors up to 1.8mm for larger conductors such as 150mm².
How does the conductor diameter vary between minimum and maximum limits?
Conductor diameters are tightly controlled. For instance, a 25mm² conductor has a minimum diameter of 5.8mm and a maximum of 6.3mm, while a larger 150mm² conductor ranges from 13.9mm to 15.0mm.