+86 13777722188
0102030405
China Suppliers ABC CABLE SANS 1418 Self-supporting Aerial Cable Manufacturer - High Quality Power Transmission Solutions
container
heading-type-1
div容器
| Model specification | Phase Core | Neutral Core | Complete Cable | |||||||||
| No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | Overall Diameter (Approx.) | Weight (Approx.) | |||
| MIN | MAX | MIN | MAX | |||||||||
| ABC 2X16 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 14.2 | 127 |
| ABC 4X16 | 3X16 | 7 | 4.6 | 5.1 | 1.2 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 17.1 | 253 |
| ABC 2X25 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 17.2 | 193 |
| ABC 4X25 | 3x25 | 7 | 5.8 | 6.3 | 1.4 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 20.8 | 387 |
| ABC 2X35 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 20.2 | 263 |
| ABC 4X35 | 3x35 | 7 | 6.8 | 7.3 | 1.6 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 24.4 | 527 |
| ABC 2X50 | 1x50 | 7 | 7.9 | 8.4 | 1.6 | 1x50 | 7 | 7.9 | 8.4 | 1.6 | 21.8 | 338 |
| Model specification | Phase Core | Neutral Core | Complete Cable | |||||||||
| No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | Overall Diameter (Approx.) | Weight (Approx.) | |||
| MIN | MAX | MIN | MAX | |||||||||
| ABC 3X25+54.6 | 3x25 | 7 | 5.8 | 6.3 | 1.4 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 23.2 | 491 | |
| ABC 3X35+54.6 | 3x35 | 7 | 6.8 | 7.3 | 1.6 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 26 | 596 | |
| ABC 3X50+54.6 | 3x50 | 7 | 7.9 | 8.4 | 1.6 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 27.7 | 708 | |
| ABC 3X70+54.6 | 3x70 | 19 | 9.7 | 10.2 | 1.8 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 31.9 | 937 | |
| ABC 3X70+70 | 3x70 | 19 | 9.7 | 10.2 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | 32.5 | 943 | |
| ABC 3X95+54.6 | 3x95 | 19 | 11 | 12 | 1.8 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | 35 | 1174 | |
| ABC 3X95+70 | 3x95 | 19 | 11 | 12 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | 35.6 | 1214 | |
| ABC 3X120+70 | 3x120 | 19 | 12.5 | 13.5 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | 37.6 | 1424 | |
| ABC 3X150+70 | 3x150 | 19 | 13.9 | 15 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | 40.7 | 1679 | |
| Model specification | Phase Core | Neutral Core | Complete Cable | |||||||||
| No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | Overall Diameter (Approx.) | Weight (Approx.) | |||
| MIN | MAX | MIN | MAX | |||||||||
| ABC 3X25+54.6+kx16 | 3x25 | 7 | 5.8 | 6.3 | 1.4 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X35+54.6+kx16 | 3x35 | 7 | 6.8 | 7.3 | 1.6 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X50+54.6+kx16 | 3x50 | 7 | 7.9 | 8.4 | 1.6 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X70+54.6+kx25 | 3x70 | 19 | 9.7 | 10.2 | 1.8 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X70+70+kx25 | 3x70 | 19 | 9.7 | 10.2 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | / | / | |
| ABC 3X95+54.6+kx16 | 3x95 | 19 | 11 | 12 | 1.8 | AAAC 54.6 | 7/3.15 | 9.45 | 1.6 | / | / | |
| ABC 3X95+70+kx16 | 3x95 | 19 | 11 | 12 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | / | / | |
| ABC 3X120+70+kx16 | 3x120 | 19 | 12.5 | 13.5 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | / | / | |
| ABC 3X150+70+kx16 | 3x150 | 19 | 13.9 | 15 | 1.8 | AAAC 70 | 7/3.50 | 10.5 | 1.6 | / | / | |
Lighting Cores Note: Users can add one or two lighting wires to the above product structure according to their own needs. The specifications of the lighting wires are 16MM² and 25MM².
Frequently Asked Questions
What are the available conductor sizes for the ABC phase cores?
According to the specifications, the phase core sizes range from 16mm² up to 150mm² (such as 3x25, 3x70, 3x120, and 3x150) depending on the selected model.
Can street lighting wires be added to the ABC cable structure?
Yes, users can add one or two lighting wires to the standard product structure according to specific installation needs. The standard specifications for these lighting wires are 16mm² and 25mm².
What type of material is used for the neutral core in these cables?
The neutral core options include standard copper/aluminum cores or AAAC (All Aluminum Alloy Conductor) specifications like AAAC 54.6 and AAAC 70, which provide supporting strength to the cable bundle.
What is the typical insulation thickness of these cables?
The insulation thickness varies depending on the core cross-section area, ranging from 1.2mm for smaller cores (16mm²) up to 1.8mm for larger cores (70mm² to 150mm²).
How does the cable weight scale with the model specifications?
The approximate weight scales with the core size and configuration. For example, a basic ABC 2X16 cable weighs approximately 127 kg/km, while a larger ABC 3X150+70 configuration weighs approximately 1679 kg/km.