+86 13777722188
China ACSR Steel Core Aluminum Alloy Conductor Suppliers | High-Quality Power Transmission Factory Products
heading-type-1
| Nominal Area | Sectional Area | Wire Diameter & Stranding | Diameter of Conductor | Linear Mass | Rated Strength | Max. D.C. Resistance at 20℃ | |||||
| Aluminum alloy | Steel | Total | Aluminum alloy | Steel | |||||||
| mm² | mm² | mm² | mm² | mm | No | mm | No | mm | kg/km | kN | Ω/km |
| 26 | 18.4 | 3.07 | 21.5 | 1.98 | 6 | 1.98 | 1 | 5.93 | 74.8 | 9.02 | 1.7934 |
| 25 | 28.8 | 4.80 | 33.6 | 2.47 | 6 | 2.47 | 1 | 7.41 | 116.3 | 13.96 | 1.1478 |
| 40 | 46.0 | 7.67 | 53.7 | 3.13 | 6 | 3.13 | 1 | 9.38 | 186.8 | 22.02 | 0.7174 |
| 63 | 72.5 | 12.1 | 84.6 | 3.92 | 6 | 3.92 | 1 | 11.8 | 293.0 | 34.68 | 0.4555 |
| 100 | 115 | 6.39 | 121 | 2.85 | 18 | 2.85 | 1 | 14.3 | 366.0 | 41.24 | 0.2880 |
| 125 | 144 | 7.99 | 152 | 3.19 | 18 | 3.19 | 1 | 16.0 | 458.6 | 51.23 | 0.2304 |
| 125 | 144 | 23.4 | 167 | 2.65 | 26 | 2.06 | 7 | 16.8 | 579.4 | 69.86 | 0.2310 |
| 160 | 184 | 10.2 | 194 | 3.61 | 18 | 3.61 | 1 | 18.0 | 587.3 | 65.58 | 0.1800 |
| 160 | 184 | 30.0 | 214 | 3.00 | 26 | 2.34 | 7 | 19.0 | 743.0 | 88.52 | 0.1805 |
| 200 | 230 | 12.8 | 243 | 4.04 | 18 | 4.04 | 1 | 20.2 | 735.6 | 81.97 | 0.1440 |
| 200 | 230 | 37.5 | 268 | 3.36 | 26 | 2.61 | 7 | 21.3 | 931.0 | 110.64 | 0.1444 |
| 250 | 288 | 28.3 | 316 | 4.08 | 22 | 2.27 | 7 | 23.1 | 1016.6 | 117.09 | 0.1154 |
| 250 | 288 | 46.9 | 335 | 3.75 | 26 | 2.92 | 7 | 23.8 | 1161.5 | 138.31 | 0.1155 |
| 315 | 383 | 25.1 | 408 | 3.20 | 45 | 2.14 | 7 | 25.8 | 1198.0 | 136.28 | 0.0917 |
| 315 | 383 | 59.0 | 442 | 4.21 | 26 | 3.28 | 7 | 26.7 | 1464.4 | 171.90 | 0.0917 |
| 400 | 460 | 31.8 | 492 | 3.61 | 45 | 2.41 | 7 | 28.9 | 1523.8 | 172.10 | 0.0722 |
| 400 | 460 | 59.7 | 520 | 3.29 | 54 | 3.29 | 7 | 29.7 | 1736.9 | 201.46 | 0.0723 |
| 450 | 518 | 35.8 | 554 | 3.83 | 45 | 2.55 | 7 | 30.6 | 1713.7 | 193.61 | 0.0642 |
| 450 | 518 | 67.1 | 585 | 3.49 | 54 | 3.49 | 7 | 31.5 | 1954.5 | 226.64 | 0.0643 |
| 500 | 575 | 39.8 | 615 | 4.04 | 45 | 2.69 | 7 | 32.3 | 1906.8 | 215.12 | 0.0578 |
| 500 | 575 | 74.6 | 650 | 3.68 | 54 | 3.68 | 7 | 33.2 | 2173.1 | 251.82 | 0.0578 |
| 560 | 645 | 44.6 | 689 | 4.27 | 45 | 2.85 | 7 | 34.2 | 2131.8 | 240.93 | 0.0516 |
| 560 | 645 | 81.6 | 726 | 3.90 | 54 | 2.34 | 19 | 35.1 | 2425.7 | 283.21 | 0.0516 |
| 630 | 725 | 31.3 | 756 | 3.58 | 72 | 2.39 | 7 | 35.8 | 2250.4 | 249.62 | 0.0459 |
| 630 | 725 | 91.8 | 817 | 4.13 | 54 | 2.48 | 19 | 37.2 | 2721.4 | 318.61 | 0.0459 |
| 710 | 817 | 35.3 | 852 | 3.80 | 72 | 2.53 | 7 | 38.0 | 2534.0 | 281.32 | 0.0407 |
| 710 | 817 | 104 | 921 | 4.39 | 54 | 2.63 | 19 | 39.5 | 3071.0 | 359.98 | 0.0407 |
| 800 | 921 | 39.8 | 961 | 4.04 | 72 | 2.69 | 7 | 40.4 | 2864.2 | 316.98 | 0.0361 |
| 800 | 921 | 76.7 | 997 | 3.74 | 84 | 3.74 | 7 | 41.1 | 3156.3 | 356.03 | 0.0362 |
| 900 | 1036 | 44.8 | 1081 | 4.28 | 72 | 2.85 | 7 | 42.8 | 3214.7 | 356.6 | 0.0321 |
| 900 | 1036 | 86.3 | 1122 | 3.96 | 84 | 3.96 | 7 | 43.6 | 3538.6 | 400.53 | 0.0322 |
| 1000 | 1151 | 93.7 | 1245 | 4.18 | 84 | 2.51 | 19 | 45.9 | 3926.6 | 446.37 | 0.0289 |
| 1120 | 1289 | 105 | 1394 | 4.42 | 84 | 2.65 | 19 | 48.6 | 4387.8 | 499.93 | 0.0258 |
The nominal area is the designated standard cross-sectional size (in mm²) used for reference and sizing classification, representing the overall carrying capacity category of the overhead conductor.
The galvanized or reinforced steel core provides the primary mechanical tensile strength (measured in kN), allowing long-span transmission installations while preventing excessive conductor sagging under high mechanical stress.
20°C (68°F) serves as the international baseline reference temperature for electrical conductivity standards, ensuring uniform measurement of power loss and electrical efficiency across various cable cross-sections.
The total sectional area is the combined sum of the individual aluminum alloy conducting strands area and the central structural steel reinforcement core area (Total Area = Aluminum Area + Steel Area).
Linear mass dictates the self-weight loading per kilometer of conductor, which is critical for calculating tower structural load bearing, tension limits, insulator stress, and aerodynamic wind/ice loading dynamics.
The stranding configuration defines the count and diameter of outer aluminum alloy wires (for current conduction) and inner steel wires (for mechanical support), ensuring optimal flexibility, strength, and electrical performance.