| Model specification | Phase Core | Neutral Core | Complete Cable | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | No.& Section Area | No.of wire | Dia.of Conductor | Insulation Thickness | Overall Diameter (Approx.) | Weight (Approx.) | |||
| MIN | MAX | MIN | MAX | |||||||||
| ABC 2X16 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 14.2 | 127 |
| ABC 4X16 | 3X16 | 7 | 4.6 | 5.1 | 1.2 | 1X16 | 7 | 4.6 | 5.1 | 1.2 | 17.1 | 253 |
| ABC 2X25 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 17.2 | 193 |
| ABC 4X25 | 3x25 | 7 | 5.8 | 6.3 | 1.4 | 1x25 | 7 | 5.8 | 6.3 | 1.4 | 20.8 | 387 |
| ABC 2X35 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 20.2 | 263 |
| ABC 4X35 | 3x35 | 7 | 6.8 | 7.3 | 1.6 | 1x35 | 7 | 6.8 | 7.3 | 1.6 | 24.4 | 527 |
| ABC 2X50 | 1x50 | 7 | 7.9 | 8.4 | 1.6 | 1x50 | 7 | 7.9 | 8.4 | 1.6 | 21.8 | 338 |
| Core number and nominal cross-sectional area(mm2) | Resistance at 20 °C Ω/km Max. | Continuous amapcity (A) | Voltage drop cos φ=0,8 ( V/A/km ) | The length of the tray suitable for container loading(m/drum) | N.W. kg/drum | G.W. kg/drum | Volume m³/drum | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ABC 2×16 | 1.91 | 93 | 3.98 | 5000 | 635 | 740 | 1.46 | |||||
| ABC 4×16 | 1.91 | 83 | 3.44 | 2500 | 633 | 738 | 1.46 | |||||
| ABC 2×25 | 1.2 | 122 | 2.54 | 3400 | 656 | 761 | 1.46 | |||||
| ABC 4×25 | 1.2 | 111 | 2.2 | 1700 | 658 | 763 | 1.46 | |||||
| ABC 2×35 | 0.868 | 138 | 1.65 | 2400 | 631 | 736 | 1.46 | |||||
| ABC 4×35 | 0.868 | 138 | 1.65 | 1200 | 632 | 737 | 1.46 | |||||
| ABC 2×50 | 0.641 | 168 | 1.27 | 2000 | 676 | 781 | 1.46 | |||||
i
Note: Size of the wooden drum is 1140 * 1120 mm.
❓ Frequently Asked Questions (FAQ)
Q1: What is the continuous ampacity range for these ABC cables?
The continuous ampacity of these ABC cables ranges from 83 A (for ABC 4x16) up to 168 A (for ABC 2x50), depending on the specific core configuration and cross-sectional area.
Q2: What is the maximum conductor resistance at 20 °C for ABC 2x16 and 4x16 cables?
The maximum conductor resistance at 20 °C for both ABC 2x16 and ABC 4x16 cables is 1.91 Ω/km.
Q3: What are the packaging specifications and drum sizes for shipping?
The standard size of the wooden drum used for container loading is 1140 * 1120 mm, with a volume of approximately 1.46 m³ per drum. Gross weights range between 736 kg/drum and 781 kg/drum depending on the cable specifications.
Q4: How does insulation thickness vary across different ABC cable models?
The insulation thickness is designed according to the cable size: it is 1.2 mm for the 16 mm² models, 1.4 mm for the 25 mm² models, and 1.6 mm for the 35 mm² and 50 mm² models.
Q5: What are the min and max conductor diameters for ABC 2x50 cables?
For the ABC 2x50 model specification, the conductor diameter has a minimum limit of 7.9 mm and a maximum limit of 8.4 mm.