Leave Your Message

0.6/1kV ABC Cable AS 3560.1 - High-Quality China Supplier & Factory for Durable Electrical Solutions

,

Standards: AS 3560.1

,

CONSTRUCTION
Ⅰ、Available in 2, 3, or 4-core configurations;
Ⅱ、Phase and neutral conductors are of equal size and type;
Ⅲ、Conductor sizes range from 16 mm2 to 150 mm2;

,

Phase Conductor
Features a circular stranded, rounded, compacted aluminum construction for enhanced conductivity and durability.

,

Neutral (Messenger) Conductor
Also crafted from circular stranded, rounded, compacted aluminum to ensure consistent performance.

,

Insulation
The insulation is made from black, cross-linked polyethylene (XLPE) for superior thermal and electrical properties.

,

Our products are manufactured in China, with a focus on quality control and innovation, making us a leading supplier and factory in the electrical cable industry.

,
    container

    heading-type-1

    div容器

    Type of conductor or core Nominal cross-sectional area mm² (Core) Number of wires min. Resistance at 20 °C Ω/km Max. Dia. of Conductor Breaking force (N) Thickness of dielectric mm Outside diameter mm
    MIN MAX MIN MAX
    Phase or neutral (aluminium) 16(2/4) 6 1.91 4.5 4.8 2200 1.3 7.1 7.9
    25(2/3/4) 6 1.20 5.8 6.1 3500 1.3 8.4 9.2
    35(2/3/4) 6 0.868 6.8 7.2 4900 1.3 9.4 10.3
    50(2/3/4) 6 0.641 8.0 8.4 7000 1.5 11 11.9
    70(4) 12 0.443 9.6 10.1 9800 1.5 12.6 13.6
    95(2/4) 15 0.320 11.3 11.9 13300 1.7 14.7 15.9
    120(4) 15 0.253 12.8 13.5 16800 1.7 16.2 17.5
    150(4) 15 0.206 14.1 14.9 21000 1.7 17.5 18.9
    Frequently Asked Questions
    What is the maximum DC resistance of a 16 mm² aluminium conductor at 20 °C?
    According to the technical specifications, the maximum electrical resistance for a 16 mm² nominal cross-sectional area aluminium conductor at 20 °C is 1.91 Ω/km.
    How does the conductor cross-sectional area affect the minimum breaking force?
    The minimum breaking force increases proportionally with the nominal cross-sectional area. It ranges from 2200 N for a 16 mm² conductor up to 21000 N for a 150 mm² conductor.
    What is the required insulation (dielectric) thickness for these aluminium conductors?
    The thickness of the dielectric material varies depending on the core size: 1.3 mm for sizes 16 mm² to 35 mm², 1.5 mm for sizes 50 mm² and 70 mm², and 1.7 mm for larger sizes ranging from 95 mm² to 150 mm².
    What are the minimum and maximum outside diameters for a 95 mm² conductor?
    For a 95 mm² aluminium conductor, the minimum outside diameter is 14.7 mm and the maximum outside diameter is 15.9 mm.
    How many minimum wires are required for a 70 mm² aluminium conductor?
    A 70 mm² nominal cross-sectional area aluminium conductor requires a minimum of 12 wires in its structural layout.