0.6/1kV ABC Cable AS 3560.1 - High-Quality Aluminum Conductors from China Suppliers and Factory
container
heading-type-1
div容器
| Type of conductor or core | Nominal cross- sectional area mm2(Core) | Number of wires min. | Resistance at 20 °C Ω/km Max. | Dia.of Conductor | Breaking force (N) | Thickness of dielectric mm | Outside diameter mm | |||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| MIN | MAX | MIN | MAX | |||||||||
| Phase or neutral (aluminium) | 16(2/4) | 6 | 1.91 | 4.5 | 4.8 | 2200 | 1.3 | 7.1 | 7.9 | |||
| 25(2/3/4) | 6 | 1.20 | 5.8 | 6.1 | 3500 | 1.3 | 8.4 | 9.2 | ||||
| 35(2/3/4) | 6 | 0.868 | 6.8 | 7.2 | 4900 | 1.3 | 9.4 | 10.3 | ||||
| 50(2/3/4) | 6 | 0.641 | 8.0 | 8.4 | 7000 | 1.5 | 11 | 11.9 | ||||
| 70(4) | 12 | 0.443 | 9.6 | 10.1 | 9800 | 1.5 | 12.6 | 13.6 | ||||
| 95(2/4) | 15 | 0.320 | 11.3 | 11.9 | 13300 | 1.7 | 14.7 | 15.9 | ||||
| 120(4) | 15 | 0.253 | 12.8 | 13.5 | 16800 | 1.7 | 16.2 | 17.5 | ||||
| 150(4) | 15 | 0.206 | 14.1 | 14.9 | 21000 | 1.7 | 17.5 | 18.9 | ||||
Frequently Asked Questions
What is the maximum electrical resistance for a 16 mm² aluminium conductor?
According to the technical specifications, the maximum electrical resistance for a 16 mm² aluminium phase or neutral conductor at 20 °C is 1.91 Ω/km.
How does the breaking force scale with nominal cross-sectional area?
The breaking force increases proportionally with the conductor's cross-sectional area. It starts at 2200 N for a 16 mm² conductor and goes up to 21000 N for a 150 mm² conductor.
What is the dielectric thickness range for these conductors?
The dielectric (insulation) thickness varies depending on the core size: it is 1.3 mm for sizes 16 mm² to 35 mm², 1.5 mm for sizes 50 mm² and 70 mm², and 1.7 mm for larger sizes ranging from 95 mm² to 150 mm².
What are the minimum and maximum outside diameters for a 120 mm² conductor?
For a 120 mm² nominal cross-sectional area conductor, the minimum outside diameter is 16.2 mm and the maximum outside diameter is 17.5 mm.
How many minimum wires are required for conductors sized 70 mm² and above?
Conductors with a nominal cross-sectional area of 70 mm² require a minimum of 12 wires, whereas larger sizes (95 mm², 120 mm², and 150 mm²) require a minimum of 15 wires.